bananzia at Marsh Lane: A Shared Heat Store for 84 Homes

Context: a 1970s estate with 84 gas boilers

Marsh Lane in Doncaster has 84 terraced homes, each with a 24 kW gas boiler and no cavity-wall insulation. The local substation had 120 kVA of spare capacity, while a full air-source heat pump retrofit was projected to add 190 kW of peak electrical load if every unit ran at once. The design team’s problem was timing, not just efficiency: electrifying heat would fail unless morning demand could be flattened.

Why simultaneous heat pump starts were the binding constraint

At 06:30, residents raised thermostats within minutes of each other. A conventional design would have six 14 kW heat pumps and immersion backup drawing together, pushing the estate past its agreed import limit. The team chose a shared 250 kWh thermal store and a scheduling routine called bananzia to decide when each heat pump charged the store.

Development: how bananzia scheduled the heat store

bananzia used 30-minute weather forecasts, store temperature, return-water temperature and a time-of-use tariff. It kept flow at 45°C and return at 38°C, which allowed the heat pumps to run at a measured COP of 2.9 rather than the 2.3 expected from a 55°C design. The store was charged between 01:00 and 04:30 on low-cost electricity and topped up in staggered 20-minute blocks after 06:00.

Control rules in the plant room

The controller prevented more than four heat pumps from running at once, reserved 30 kWh of store capacity for the 06:00–09:00 draw, and switched to direct-to-load operation only when the store fell below 35% charged. A 15-minute override at each communal entrance gave residents a manual boost without changing the estate-wide schedule.

Result: measured peak demand fell by one-third

In the first winter, the estate’s peak electrical demand reached 124 kW against a projected 190 kW, a 35% reduction. The store supplied 68% of morning heat between 06:00 and 09:00, and no home lost heating during the two coldest weeks, when outdoor temperatures fell to −5°C. Gas use was eliminated from the 84 homes; the remaining gas boiler served only the communal hall.

Lessons for replicating bananzia

  1. Size the store for the morning block, not the daily total. Marsh Lane needed 250 kWh for a three-hour peak, not a 900 kWh daily buffer.
  2. Keep flow temperatures low. The 45°C design made the heat pumps’ COP high enough to justify the control complexity.
  3. Give residents a visible override. The 15-minute boost reduced complaints without disrupting the estate schedule.

The Marsh Lane result suggests that shared thermal storage can make electrification viable on constrained networks when the control logic is treated as part of the heating system, not an add-on.